| Availability: | |
|---|---|
It can be widely deployed for peak shaving, dynamic capacity expansion, and off-grid power supply scenarios.
Safety & Reliability
High Efficiency & Versatility
Seamless transition between grid-tied and off-grid modes.
Adaptable strategies for various scenarios: no grid, weak grid, or solar power.
Maximizes solar consumption and generator efficiency for significant cost reduction.
Capable of 100% three-phase imbalance and 200% short-term overload.
Flexible Deployment
Highly integrated, all-in-one design combining storage, generator, and charging.
Mobile, pre-assembled containerized solution; power availability in as little as one week.
Built-in MPPT solar charge controller.
Intelligence & User-Friendliness
Equipped with a bypass mode.
Moreover, its trailer-mounted design allows for easy transportation and redeployment — like a large-scale mobile power bank — flexibly matching dynamic operational demands and turning power supply into a mobile, reliable asset.
Lower Operating Costs
Tightening carbon emission standards, low-emission zone policies, and noise restrictions have increased the cost of traditional diesel-only solutions.
FusionCab's hybrid microgrid prioritizes clean, locally generated solar power — significantly reducing carbon emissions and noise pollution, while ensuring compliance with environmental regulations and protecting nearby communities.
The system's IP54 + C3 protection rating further enhances durability and energy efficiency, making it a quiet, green, and reliable power solution.
| Item | iEZA-261KLB-250K | |
| Battery Parameters | Cell Specifications | Lithium Iron Phosphate (LFP), 314Ah |
| Rated Capacity | 261.248kWh | |
| Rated Voltage | 832V | |
| Operating Voltage Range | 702V-949V | |
| Charge/Discharge Rate | ≤0.5C | |
| Depth of Discharge | 95%DOD | |
| Utility Power Interface Parameters | Grid Voltage | 400V(-10%~15%) |
| Rated Power | 125kW | |
| Rated Current | 189A | |
| Rated Frequency | 50Hz | |
| Wiring Configuration | L1/L2/L3/N/PE (OT terminals) | |
| Power Factor | >0.99 (Adjustable 1 Leading ~ 1 Lagging) | |
| THDi | <3% (Rated Power) | |
| Load Interface Parameters | Rated Capacity | 130kVA |
| Maximum Output Power | 250kVA (233kVA @ battery-only mode, bypass excluded) | |
| Overload Duration | ≤3s | |
| Rated Output Voltage | 400V(-10%~15%) | |
| Rated Output Frequency | 50Hz | |
| Wiring Configuration | L1/L2/L3/N/PE (OT terminals) | |
| Grid-On/Off Switching Time | 0ms (typical) | |
| PV Interface Parameters | Maximum String Voltage | ≤650VDC |
| Wiring Configuration | PV+/PV- (connected to OT terminals after PV array combiner) | |
| Maximum Input Current | ≤100A @ MPPT rated power 50kW | |
| MPPT Rated Power | 50kW (100kW optional) | |
| Diesel Generator System Parameters | Rated Power | 60kW |
| Fuel Tank Capacity | Approx. 150L fuel tank | |
| System Parameters | Cooling Method | Battery system: intelligent liquid cooling; Others: forced air cooling |
| Dimensions (W×D×H) | 2438*2600*2991mm | |
| Weight | <9t | |
| Protection Level (IP Rating) | IP54 (battery compartment) | |
| Relative Humidity | ≤95%, Non-condensing | |
| Operating Temperature | -25℃~50℃ (>45°c Derating) | |
| Maximum Operating Altitude | 4000m(>3000m Derating) | |
| Cycle Life | 6,000 Cycles @ 70% EOL | |
| Fire Protection Configuration | Perfluorohexanone (PACK level) | |
| Optional Accessories | Single-phase AC charging (7kW); Wall-mounted AC charging station |