| Availability: | |
|---|---|
It can be widely deployed for peak shaving, dynamic capacity expansion, and off-grid power supply scenarios.
Safety & Reliability
High Efficiency & Versatility
Seamless transition between grid-tied and off-grid modes.
Adaptable strategies for various scenarios: no grid, weak grid, or solar power.
Maximizes solar consumption and generator efficiency for significant cost reduction.
Capable of 100% three-phase imbalance and 200% short-term overload.
Flexible Deployment
Highly integrated, all-in-one design combining storage, generator, and charging.
Mobile, pre-assembled containerized solution; power availability in as little as one week.
Reserved PV installation interface
Intelligence & User-Friendliness
Moreover, its trailer-mounted design allows for easy transportation and redeployment — like a large-scale mobile power bank — flexibly matching dynamic operational demands and turning power supply into a mobile, reliable asset.
Lower Operating Costs
Tightening carbon emission standards, low-emission zone policies, and noise restrictions have increased the cost of traditional diesel-only solutions.
FusionCab's hybrid microgrid prioritizes clean, locally generated solar power — significantly reducing carbon emissions and noise pollution, while ensuring compliance with environmental regulations and protecting nearby communities.
The system's IP54 + C3 protection rating further enhances durability and energy efficiency, making it a quiet, green, and reliable power solution.
| Item | iEZA-1044KLB-650K | ||
| Battery Parameters | Cell Specifications | Lithium Iron Phosphate (LFP),314Ah | |
| Rated Capacity | 1044.992kWh | ||
| Rated Voltage | 832V | ||
| Operating Voltage Range | 702V-949V | ||
| Charge/Discharge Rate | ≤0.5C | ||
| Depth of Discharge | 95%DOD | ||
| Utility Power Interface Parameters | Grid Voltage | 400V(-10%~15%) | |
| Rated Power | 650kW | ||
| Rated Current | 987A | ||
| Rated Frequency | 50Hz | ||
| Wiring Configuration | L1/L2/L3/N/PE (OT terminals) | ||
| Power Factor | >0.99 (Adjustable 1 Leading ~ 1 Lagging) | ||
| THDi | <3% (Rated Power) | ||
| Load Interface Parameters | Grid/Off-grid Switching Time | 20ms (Typical Value) | |
| Rated Capacity | 520kVA | ||
| Maximum Output Capacity | 650kW | ||
| Overload Duration | ≤3s | ||
| Rated Output Voltage | 400V (-10%~15%) | ||
| Rated Output Frequency | 50 Hz | ||
| Wiring Configuration | L1/L2/L3/N/PE (OT terminals) | ||
| PV Interface Parameters | Rated Voltage | 400V (-10%~15%) | |
| Maximum Input Power | 400kW | ||
| Diesel Generator System Parameters | Rated Power | 100 kW | |
| Fuel Tank Capacity | Approx. 250L fuel tank | ||
| System Parameters | Cooling Method | Battery system: intelligent liquid cooling; Others: forced air cooling | |
| Dimensions (W×D×H) | 6700*2200*2600mm | ||
| Weight | <16t | ||
| Protection Level (IP Rating) | IP54 (battery compartment) | ||
| Relative Humidity | ≤95%, Non-condensing | ||
| Operating Temperature | -25°c~50°c (>45°c Derating) | ||
| Maximum Operating Altitude | 4000m (>3000m Derating) | ||
| Cycle Life | 6,000 Cycles @ 70% EOL | ||
| Fire Protection Configuration | Perfluorohexanone (PACK level) | ||